TECO VFD Fault Code List & Troubleshooting (OC/OU/LU/OH/OL/GF)

Source:WEIMA-ELECTRIC Date:2026-10-14 17:15:41 Views: 1

Customers running TECO VFDs (TECO VFD series such as JNI, K, etc.) most often ask one thing: "what does the code on the screen mean?" We ranked the high-frequency alarms by how often they show up, and paired each with on-site troubleshooting steps you can follow directly. Bookmark this page—next time a fault pops up, don't rush to call service; you can clear more than half of them yourself.

1. TECO VFD Common Fault Code Quick Reference

CodeMeaningMost Common Cause
OCOver CurrentHeavy load, motor short, accel time too short
OU / OVOver VoltageDecel too fast, inertial load regen, brake resistor missing
LUUnder VoltageLow input voltage, loose wiring, momentary power loss
OHInverter Over HeatFan stopped, heatsink clogged, high ambient temp
OLMotor Over LoadMechanical jam, wrong rated current set, undersized VFD
GFGround FaultMotor/cable insulation damaged, damp-environment leakage

2. Step-by-Step Fixes (On-Site)

1. OC Over Current — TECO VFD OC overcurrent fix

Don't reset yet. First measure the 3-phase motor current with a clamp meter and check balance; a deviation over 5% usually means insulation aging or a winding short. Second, check whether a contactor was mistakenly added on the output side (frequent switching triggers surge). Third, extend the acceleration time or raise the low-frequency torque compensation. If OC persists, disconnect the motor leads and measure insulation resistance—three-phase balance is normal.

2. OU/OV Over Voltage — TECO VFD OU overvoltage cause

Usually appears when decel is too fast or a heavy-inertia load feeds energy back. Fix: extend decel time to ~1.5× the factory value; add a brake resistor; confirm DC-bus voltage stays under the limit (e.g. T4 class ~750V). If the grid is unstable, add an ACL input reactor.

3. LU Under Voltage — TECO VFD LU undervoltage fix

Check that 3-phase input voltage is not below 10% of rated, terminals are tight, and there is no momentary dropout. With insufficient supply capacity, match the VFD and front-end breaker properly to avoid DC-bus undervoltage trips.

4. OH Over Heat — TECO VFD OH overheat reset

Clean the heatsink dust, check the fan, confirm cabinet temperature. Only re-power after it cools down. In hot workshops, derate or add a separate air duct. TECO VFD alarm reset: after clearing the cause, press Reset on the panel or re-power; if it repeats, don't force-reset—inspect load and supply.

5. OL Overload & GF Ground Fault

OL: verify motor nameplate current vs VFD rated current, then check for mechanical jam. GF: megger the motor ground insulation; below 0.5MΩ means replace the cable or motor—especially in damp sites.

3. TECO VFD Factory Reset & Parameter Setting

When commissioning goes wrong, a TECO VFD factory reset saves time: enter the parameter menu and execute the "INIT / initialize" item (exact key path varies by model—see the manual). TECO VFD parameter setting core: first enter motor nameplate data (power, voltage, current, rpm) and run autotune, then set the overload curve by load type (ND for fan/pump, HD for constant torque). Unsure? Ask your distributor engineer for a model-specific parameter sheet.

4. FAQ

Q: How do I clear an "Err" display?
A: "Err" is generic—read which one (OC/OU/LU…), fix per the steps above, then reset. If it keeps returning, it's a hardware or load issue needing on-site inspection.

Q: What carrier frequency should I set?
A: Factory environments: 2.5–5kHz. Lower = more stable, less EMI; higher = quieter but hotter. Don't raise it for long heavy loads in high heat.

Q: Are faults worse in summer?
A: Yes. Heat is the #1 enemy of VFDs; with poor cooling, OC/OH alarms can double. Clean dust regularly and keep ventilation.